EN1403 - 16A - 3Phase Metered Enlogic PDU
          The EN1403 Input Metered PDU includes energy metering with advanced power and environmental monitoring options. Metering at the phase input and internal circuit breaker levels allow comprehensive overload monitoring and advanced alerts, while billing-grade watt-hour metering provides accurate power consumption data for energy use optimization and change management. Advanced network management features allow for a variety of remote access methods and integration with accessories including environmental monitoring and security access solutions.
         
		  The EN1403 Input Metered PDU includes energy metering with advanced power and environmental monitoring options. Metering at the phase input and internal circuit breaker levels allow comprehensive overload monitoring and advanced alerts, while billing-grade watt-hour metering provides accurate power consumption data for energy use optimization and change management. Advanced network management features allow for a variety of remote access methods and integration with accessories including environmental monitoring and security access solutions. 
         
	• Network Connectivity - Dual ports: 1x Gigabit Ethernet (10/100/1000 Mbps) and 1x (10/100 Mbps)
• Ethernet Cascading - Up to 64 units share a single “daisy-chain” Ethernet IP address
• DC Power Sharing - Each PDU can provide DC power sufficient to power network management electronics and sensors in a neighbouring PDU in the event of AC power source loss
• Dual Ethernet Support - Dual Ethernet ports for redundant communication
• Dual Network Access - Dual network connectivity allows redundancy and Multiple stockholder connectivity for up to 64 units in Ethernet cascading mode
• Remote Connectivity - HTTP(s), iPV4 and iPV6, SSH, Virtual Serial, SNMP (v1, v2c, v3), JSON-RPC, LDAP(S), FTP/SFTP, RADIUS, Redfish DMTF RESTful API
• WebUI Interfacce - Data efficient REACT framework with native mobile device support
         .jpg) Metering & Switching
         
		 Metering & Switching
Metering Attributes	Voltage(V),Current(A),Apparent Power(kVA),Real Power(kW),Power Factor,Energy(kWH)
Metering Accuracy	± 1% to ISO/IES 62052-21
Metering Location	Input Phase and circuit breaker measurements
Remote Outlet Switching	No
Electrical
Electrical Input
Acceptable input voltage	400V 3ph Wye
Input current (phase)	16A
Input frequency	50/60 Hz
Max Input power	11.5 kVA @ 240 VAC
Input Plug	IEC 60309 516P6
Electrical Output
Output voltage	230VAC
Maximum output current (phase)	32A
Overload protection (internal)	0, n/a
Outlet configuration	(36)C13, (6)C19
Physical
Chassis Dimensions (L x W x D)	1750.0mmx52.0mmx53.0mm
Depth at circuit breaker	N/A
Input cord length	3m (10 ft)
Environmental
Operating Temperature -5 to 60°C (23 to 140°F)
Storage Temperature -20 to 60°C (-4 to 140°F)
Humidity (operating/storage) 5-90% RH / 5-95% RH; non-condensing
Max operating elevation 3,000 m (9,840 ft)
Compliance
Safety verification CE, Demko Certified to IEC/EN60950-1, RoHS, REACH
Environmental ROHS, REACH
* BTO - 2 Week Manufacturing Lead Time *